1®AMERICA’S BOILER COMPANYBurnhamCorporationLancaster, PA 17604-3079INSTALLATION, OPERATINGANDSERVICE INSTRUCTIONSALLIANCETM SERIESINDIRECT-FIRED WAT
10G. Connect water boiler supplypiping (See Figures 3 thru 6).1. For a space heating system thatutilizes ZONE VALVES ANDA BOILER BYPASS, refer toFigur
113. For a space heating systemthat utilizes ZONEVALVES WITHOUT ABOILER BYPASS, refer toFigure 5. The Alliance™connection labeled"BOILER SUPPLY&
12H. Connect steam boiler piping (See Figures 7 thru 10).1. Burnham V-7 Series steam boiler (Refer to Figure7).a. For satisfactory supply of hot water
13Figure 8Typical Steam Boiler w/Connections Available Below Water LineFigure 93. Typical steam boiler with connections availablebelow the water line
14Figure 104. Steam boiler without hot water connectionsavailable below the water line (Refer to Figure 10).a. Supplying the Alliance™ from the bottom
15IV. Electrical1. Install electric wiring in accordance with NationalElectrical Code or the Canadian Electrical Codeand local regulations. See Figu
16V. OperationA. System Start-Up1. Follow boiler installation instructions to placeboiler in operation.2. Turn aquastat dial clockwise to desired sett
17VI. Service InstructionsA. The Alliance™ is intended to provide a service life ofmany years. Components that require service,however, may be subjec
18VII. Trouble ShootingPROBLEM CAUSE SOLUTIONNo hot water at faucet Boiler does not operate Refer to boiler installation instructionsCheck main servic
19VIII. Repair Parts1 Aquastat (Honeywell L4006A2114)80108127 Top CoverAL26A80408082 Handhole Cover8050802 AL40A3 Handhole Cover Gasket8200804 AL53A4
2The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels,or to important info
20All Alliance™ Series repair parts may be obtained through your local Burnham Wholesale Distributor. Should yourequire assistance in locating a Burn
21Inspection / Service ScheduleDATE INSPECTION AND/OR SERVICE PERFORMED
3I. General InformationSection I - General Information ... 3Ratings, Capacities, Weights, & Dimensions ... 4Section I
4Table 1: Alliance Water Heater Dimension (Inches)Table 2: Alliance Water Heater CapacitiesTable 3: Alliance Water Heater PerformanceALLIANCEMODELA
5II. Pre-InstallationInspect shipment carefully for any sign of damage. Allequipment is carefully manufactured, inspected andpacked. Burnham Corporati
6Select a circulator which will provide at least theminimum flow rate at combined pressure drop.B. System Zone Control The AllianceTM waterheater mus
7cool to room temperature, or if tank is drainedwithout opening a hot water faucet. A Watts®Model No. N36 is an appropriate vacuum reliefvalve.4. The
8III. PipingA. Drain domestic water system.1. Shut off cold water supply at main shut-off valve.2. Open one or more system faucets to relievepressure.
94. Purge air from domestic water system. Allow waterto run so the tank is thoroughly purged of anydebris. Run water long enough so that a minimumof